When it comes to fire extinguishers, one of the first things most people think about is accessibility. If there is a potential fire hazard, shouldn’t the fire extinguisher be as close to that hazard as possible? That seems logical. If a flammable-liquid storage tank catches fire, for example, it might seem like the best place for an extinguisher would be directly beside the tank.
But when it comes to outdoor flammable-liquid storage on a construction site, OSHA specifically establishes both a minimum and maximum distance.
Under 29 CFR 1926.152(d)(2):
“At least one portable fire extinguisher having a rating of not less than 20-B units shall be located not less than 25 feet, nor more than 75 feet, from any flammable liquid storage area located outside.”
In other words:
25 feet minimum. 75 feet maximum.
That requirement provides an important lesson in emergency planning: the closest possible location isn’t necessarily the safest location.
Why Can’t the Extinguisher Be Right Next to the Tank?
Imagine an outdoor construction site with a storage tank containing flammable liquid.
A fire starts at the tank.
If the only fire extinguisher is mounted directly next to the tank, the worker may have to approach the fire in order to retrieve it.
That creates an obvious problem.
A fire involving a flammable liquid can produce intense heat, flames, smoke, and potentially additional hazards from the fuel itself. As the fire develops, the location that seemed ideal for storing the extinguisher can quickly become an unsafe place for a worker to stand.
The worker may not be able to safely reach the extinguisher at all.
This is part of the reasoning behind establishing a minimum distance.
OSHA has addressed this concept in a Letter of Interpretation concerning the application of the requirement to a large outdoor diesel fuel tank. OSHA explained that the 25-to-75-foot range is intended to ensure that the extinguisher is neither too far away nor too close to the potential fire hazard.
The idea is straightforward:
You want the extinguisher close enough to reach, but far enough away that the fire doesn’t prevent you from reaching it.
The 75-Foot Maximum Matters Too
The other half of the equation is the 75-foot maximum.
Moving the extinguisher farther away from the flammable-liquid storage area may reduce the likelihood that a fire will block access to it, but eventually the extinguisher becomes too far away to be practically useful.
A fire extinguisher is intended to provide an opportunity to address an incipient-stage fire before it develops into a much larger emergency.
If a worker has to travel a significant distance to retrieve the extinguisher, precious time can be lost.
That’s why OSHA establishes a range rather than simply saying “at least 25 feet away.”
The extinguisher needs to be accessible, but its location also needs to account for the hazard it is intended to address.
What Does “20-B” Mean?
The requirement stated in 29 CFR 1926.152 doesn’t only establish a distance. It also specifies a minimum fire-extinguisher rating of 20-B for this particular application.
The “B” classification relates to fires involving flammable and combustible liquids. The number associated with the rating represents the relative extinguishing capability under the applicable testing system (20 square feet of fire-area).
This is important because simply placing any fire extinguisher within the required distance isn’t necessarily enough. The extinguisher needs to be appropriate for the anticipated fire hazard.
For an outdoor flammable-liquid storage area covered by §1926.152(d)(2), OSHA specifically calls for an extinguisher with a rating of at least 20-B.
Think About the Approach, Not Just the Distance
A tape measure can tell you whether an extinguisher is 25 feet from a tank. It can’t tell you whether a worker can safely reach it. That’s where good safety planning goes beyond simply satisfying a measurement. When evaluating extinguisher placement, consider the actual layout of the area.
Ask:
- Is the extinguisher between 25 and 75 feet from the storage area?
- Is it clearly visible?
- Can workers easily reach it?
- Is the path to the extinguisher unobstructed?
- Could a fire, smoke, or escaping liquid block the approach?
- Is the extinguisher appropriate for the anticipated fire?
- Could equipment, materials, temporary construction, or changing site conditions interfere with access?
A compliant location today can become a poor location tomorrow. Construction sites change constantly. Materials move, access routes change, temporary structures are installed and removed, and work areas evolve. Fire-extinguisher placement should be considered as part of that changing environment.
Don’t Put Yourself Between the Fire and Your Escape
There is another practical consideration worth remembering.
Using a portable fire extinguisher should never require a worker to put themselves in an unnecessarily dangerous position.
A worker addressing an incipient-stage fire should have a safe means of retreat. If the fire grows beyond the capability of the extinguisher, conditions become unsafe, or the worker loses the ability to control the fire, the priority should be getting away and allowing emergency responders to handle the situation.
That makes extinguisher placement particularly important.
You don’t want a worker to discover that the extinguisher is positioned on the other side of the fire.
The worker should be able to approach the extinguisher from a location that allows them to assess the fire and, if appropriate, attempt to extinguish it while maintaining a safe means of escape.
Fire Extinguisher Placement Is Part of Hazard Planning
It is tempting to treat fire extinguishers as a simple compliance item:
“We have one. Check.”
But effective fire protection involves more than possessing the equipment.
The extinguisher needs to be:
Present. Appropriate. Accessible. Maintained. Properly positioned.
And workers should know where it is.
This becomes particularly important when a jobsite contains flammable liquids, fuel storage, hot work, temporary heating equipment, or other activities that increase the potential for fire.
The location of the extinguisher should make sense in relation to those hazards.
What About Other Fire Extinguisher Requirements?
It’s important not to take the 25-to-75-foot requirement and apply it universally to every fire extinguisher on every construction site.
29 CFR 1926.152(d)(2) specifically addresses outdoor flammable-liquid storage areas.
Other OSHA requirements establish different fire-extinguisher provisions depending on the circumstances.
For example, 29 CFR 1926.150(c) contains requirements concerning fire extinguishers at construction jobsites, including requirements related to equipment, buildings, and specific hazards.
There are also additional requirements within §1926.152 concerning flammable and combustible liquids.
The lesson is that fire-extinguisher placement shouldn’t be reduced to memorizing a single distance.
Identify the hazard, determine which requirement applies, and then evaluate whether the equipment is actually accessible and appropriate for the situation.
A Simple Rule Worth Remembering
For outdoor flammable-liquid storage covered by 29 CFR 1926.152(d)(2):
20-B minimum rating.
25 feet minimum distance.
75 feet maximum distance.
That’s an easy set of numbers to remember. But the more important concept is the reason behind them. You don’t want the extinguisher so close that a fire makes it inaccessible. You don’t want it so far away that a worker can’t reach it quickly.
You want it positioned where it can actually perform its intended function.
Final Thoughts
Fire safety isn’t simply about having the right equipment.
It’s about thinking through what happens when the emergency actually occurs.
If a flammable-liquid storage tank catches fire, where will the flames go? Where will the smoke travel? What areas will become inaccessible? Where can a worker safely approach from? Where is the extinguisher located?
These questions can make the difference between equipment that exists on paper and equipment that is genuinely useful during an emergency.
OSHA’s 25-to-75-foot requirement is a good example of why closer isn’t always better.
Sometimes putting protective equipment a little farther away from the hazard is exactly what makes it more useful.
The goal isn’t simply to have a fire extinguisher nearby.
The goal is to have a fire extinguisher that you can actually reach when you need it.